LEADER PAINTS MARKETING
Fire Resistant Coatings Wall

Fire Resistant Coatings Wall

Send Inquiry

Fire Resistant Paint For Wall, Gypsum, Concrete

UGAMCOAT 07022007 System is tested and certified for 2 hour rating by Government of India's National Test House Mumbai.
Tested and Approved By UK LAB - Exova Warring ton fire


HSN CODE 32099020

FEATURES:

It is specially prepared for getting fire retardant properties in walls. Generally cement walls are not flammable but when there is fire on one side, the temperature is conducted or radiated though the walls and when the temperature rises above 200 degreed C on other side, the products like paper gets self ignited. To prevent such heat transfer, these type of intumescent coatings are used. These are useful on cement, concrete, gypsum, fiber board partitions etc. Suitable on walls, plastered surface, asbestos, cement sheets, textured finishes. This is water base coating hence is ecofriendly.


HOW IT WORKS:

It forms foam when temperature reaches 200 degrees Celsius. This foam is heat and fire resistant and almost non conductive. This keeps the surface away from heat and hence does not allow the surface to receive or conduct the heat in other areas. Also since this forms foam and a charred layer, it does not allow oxygen to reach to the surface over which it is applied. Hence it protects the surface from catching fire.


APPLICATION PROCEDURE
:

First clean the surface with emery papers. In case old paint or primer which is not fire rated is applied to the wall, remove it with paint remover or mechanically. Then apply single coat of UGAM F R PRIMER for wall. The primer can be thinned down with pure clean soft water. Primer can be applied with brush or spray. Then after minimum four hours interval apply first coat of UGAMCOAT 07022007 with brush, roller or airless spray to the surface. Allow four hours for drying. Then apply second coat of UGAMCOAT 07022007 to the surface and again allow four hours for drying. Likewise go on applying the coats of UGAMCOAT 07022007 to the surface till you achieve dry film thickness of 1000 microns for one hour rating OR 1600 microns for two hours rating. After application of final coat of UGAMCOAT 07022007 to the surface allow 24 hours curing. Then apply first coat of UGAM F R TOPCOAT WALL in desired color shade over UGAMCOAT 07022007 for protecting fire retardant coating from weather. Allow it to cure for six hours and apply second coat of UGAM F R TOPCOAT WALL. This can be applied with roller, brush or spray. The surface will now be ready after 12 hours for regular use. This coating is warranted for five years or first incidence of fire from the date of application. In case surface is exposed to fire, the coating should be re-applied to the surface.

COVERING OF PRIMER AND TOPCOAT:UGAM F R PRIMER WALL will cover 80 square feet per liter. It is to be applied single coat only. UGAM F R TOPCOAT WALL will cover 45 square feet in two coats. It is to be applied in two coats.


PROJECTS COMPLETED
1. Barclays Technology P Ltd office at Pune
2. Volkswagen office at Chakan
3. KPMG Ltd office at Pimpri
4. Bharat Forge Ltd Mundhava plant
5. ONGC offshore application at NEELAM and HEERA platform
6. Aquapharm Chemicals Ltd. Mahad

UGAMCOAT 07022007 - IN-TUMESCENT F R COATING FOR WALL IS CERTIFIED BY EXOVA WARRINGTONFIRE LABS UK. PLEASE FIND THE LINKS BELOW.

https://drive.google.com/folderview?id=0BzQju9hjSaqRa2oySzBtTjd2QXM&usp=sharing

LIVE DEMO OF OUR FIRE RETARDANT PAINTS FOR WOODEN HOUSE, STRUCTURE STEEL, ELECTRICAL CABLES.

https://www.youtube.com/watch?v=kjEfB8ijBtQ 